§ 16.32.220. Section 903.4.2 replaced—Alarms.  


Latest version.
  • Section 903.4.2 of the International Fire Code is deleted in its entirety and replaced with the following:

    903.4.2 Alarms. Approved audible/visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. An approved audible/visual sprinkler flow alarm shall be provided on the exterior of the building in an approved location above the fire department connection. An approved audible/visual sprinkler flow alarm to alert the occupants shall be provided throughout the interior of the building in accordance with sections 907.6.2 through 907.6.2.3 and NFPA 72. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.