§ 16.32.250. Section 905.2 amended—Installation Standard.  


Latest version.
  • Section 905.2 of the International Fire Code is amended by deletion of section 905.2 as published and adoption of the following:

    905.2 Installation standard. Standpipe systems shall be installed/designed as an automatic wet standpipe with a 500 gpm at 100 psi at the two hydraulic most demanding hose outlets in accordance with this section and NFPA 14. Fire department connections for standpipe systems shall be in accordance with Section 912.

(Ord. No. O-2019-04 , § 1, 1-8-2019)