§ 16.32.320. Section 1010.1.9.8 amended—Delayed egress locks.  


Latest version.
  • Section 1010.1.9.8 of the International Fire Code is amended by the deletion of the first sentence and replaced with the following:

    Approved, listed, delayed egress locks shall be permitted to be installed on doors serving any occupancy except Group A, E, and H occupancies in buildings which are equipped throughout with an automatic sprinkler system in accordance with section 903.3.1.1, and an approved automatic smoke detection system installed in accordance with section 907, provided that the doors unlock in accordance with Items 1 through 6 below.