§ 16.20.310. Section 402.2 replaced—Common halls and stairways.  


Latest version.
  • Section 402.2 of the International Property Maintenance Code is replaced with the following:

    402.2 Common halls and stairways. Every common hall and stairway shall be lighted at all times with at least a 60-watt standard incandescent light bulb or equivalent for each 200 square feet of floor area or equivalent illumination, provided the spacing between lights is not greater than 30 feet. Means of egress, including exterior means of egress, stairways shall be illuminated at all times when the building space served by the means of egress is occupied, with a minimum of 1 foot-candle at floors, landings, ramps, and treads.

(Ord. No. O-2019-02 , § 6, 1-8-2019)