§ 16.32.270. Section 907.1.3 amended - Equipment.  


Latest version.
  • Section 907.1.3 of the International Fire Code is amended by deletion of 907.1.3 as published and the adoption of the following:

    907.1.3 Equipment. Systems and components shall be listed and approved for the purpose for which they are installed. Only addressable fire alarm panels will be approved.

     Exception: Fire alarm panels that can transmit individual specific initiating device information.

    907.1.3.1 Combination fire and security panels. A fire alarm system shall not be used for any purpose other than fire protection or control of fire protection systems. Combination fire and security panels are not permitted.

    Section 907.1.3.2 Fire alarm system wiring. All fire alarm wiring shall be red jacketed wiring listed and approved for fire alarm systems.

(Ord. No. O-2019-04 , § 1, 1-8-2019)